AIRFLOW PATTERNS AND STACK PRESSURE SIMULATION IN A HIGH RISE RESIDENTIAL BUILDING LOCATED IN SEOUL

Khoukhi Maatouk

DOI: http://dx.doi.org/10.26687/archnet-ijar.v1i2.19

Abstract

Buoyancy forces due to air density difference between outdoor air and indoor air cause stack effect in high-rise buildings in cold climates. This stack effect occurs mainly at the core of the building such as the stairway and elevator shafts and causes many problems such as the energy loss caused by air flow, the blocked elevator door and discomfort due to inflowing of strong outdoor air. The main purpose of this work is to model the airflow pattern in a highrise building during the winter period by mean of COMIS. The presented building which is situated in Korea contains 30 floors above the ground level and 5 basement floors. Using COMIS, the simulation has been carried out for the entire building. However, the simulation failed due to the huge number of zones and interactions between them. Therefore, a model of building which contains 14 floors with 5 floors in the basement has been considered; and a simplified model based on the considered one has been constructed and compared with the 14 floors model. The simplified model consists on reducing the number of floors by combining a certain number of stories into one so that to enable the simulation to be carried on with a minimum number of zones and links. The result of the simulation shows that this approach could be used with accuracy still being satisfied. Therefore, the simplified procedure has been extended and applied to the high rise building model with 30 stories above the ground level and 5 stories in the basement. The effect of the exterior wall air-tightness of the building with 30 stories on the stack pressure and airflow by infiltration and/or by exfiltration has been investigated. The result shows that the total air by infiltration and/or exfiltration within the elevator shafts increases with the decrease of the level of the air-tightness of the exterior wall of the building. It has been also shown that a huge amount of air infiltrates through the shuttle and emergency elevator shafts from the basement.

Keywords

Stack pressure; airflow; COMIS; simulation; airtightness of exterior wall

Full Text:

PDF

References

Bossaer, A., Ducarme, D., Wouters, P., & Vandaele, L. (1999). An Example of Model Evaluation by Experimental Comparison: Pollutants Spread in an Apartment, Energy and Buildings, Vol. 30, pp. 53-59.

Fundamentals of the Multizone Air Flow ModelCOMIS (1990). Technical Note AIVC 29.

Hyung Yu, K., Park, J.C., Rhee, E.K. (2004). A Study on a Proper Reduction Process of Indoor Air Pollutant in Newly-Constructed High-rise Multi-Family Houses, CTBUH, October 10-13, Seoul, Korea.

Khoukhi, M., Yoshino, H., Liu, J. (2007). The Effect of the Wind Speed Velocity on the Stack Pressure in Medium-rise Buildings in Cold Region of China, Building and Environment, Vol. 42, pp. 1081-1088.

Koo, S.H., Jo, J.H., Seo, H.S., Yeo, M.S., & Kim, K.W. (2004). Influence of Architectural Elements on Stack Effect Problems in Tall Residential Buildings, CTBUH, October 10-13, Seoul, Korea.

Lovatt, E.J. & Wilson, A.G. (1994). Stack Effect in Tall Buildings, ASHREE Transactions, Vol. 100 (2), pp. 420-431.

Roulet, C.A., Furbringer, J.M., & Borchiellini, R. (1996). Evaluation of the Multizone Air flow Simulation Code COMIS, Roomvent’96, 5th Conference on Air Distribution Rooms, Seoul, Korea.

Tamblyn, R.T. (1991). Coping with Air Pressure Problems in Tall Buildings, ASHREE Transactions, Vol. 97 , (1), pp. 824-827.

Tamblyn, R.T. (1993). HVAC System Effects for Tall Buildings, ASHREE Transactions, Vol. 99 (2), pp. 789-92.

Tamura, G.T., & Wilson, A.G., (1967). Pressure Differences Caused by Chimney Effect in Three High Buildings, ASHREE Transactions, Vol. 73 (2), pp. 1-10.

Yu, J.Y., Cho, D.W., Yu, K.H., & Jung, H.K. (2004). Evaluation of Stack Effect According to theShape and the Window Area Ratios of Lobby in High-rise Buildings, CTBUH, October 10-13, Seoul, Korea.


Refbacks

  • There are currently no refbacks.




Copyright (c) 2015 International Journal of Architectural Research: ArchNet-IJAR



ABOUT US


- ISSN (Online) #1938 7806 - ArchNet-IJAR is covered by ArchNet@ MIT Libraries, Avery Index to Architectural Periodicals, EBSCO, CNKI, Pro-Quest, Scopus-Elsevier, Web of Science.

- Published work in ArchNet-IJAR is licensed under Creative Commons: CC-BY--NC-ND license, see http://creativecommons.org/licenses/by-nc-nd/3.0/

Copyrights © Archnet-IJAR 2007-2018

 
 

Hit Counter
Visitor Hits Since 15 Jan 2014